IEC140000133 V1 EN-US
Figure 9: PMU Connection Tester tool
The following steps explain how to set the PMU Connection Tester parameters in order to establish an
IEEE C37.118 connection with the PMU:
1. Set the IP stack on PMU Connection Tester to IPv4. Note that the default IP stack on PMU
Connection Tester tool is IPv6.
1MRK 504 165-UUS Rev. J Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
Transformer protection RET670 69
Commissioning manual
© 2017 - 2021 Hitachi Power Grids. All rights reserved