- 101 - UMC22-FBP FieldBusPlug / Issue: 02.2008
V 6
Universal Motor Controller UMC22-FBP
Software version 4.0
UMC22
0
V
10
24
V
11
24
V
12
DI
0
13
DI
1
14
DI
2
15
DI
3
16
DI
4
17
DI
5
18
5
DO
C
T1 T2 7
DO
0
6
DO
C
8
DO
1
9
DO
2
DI3* DI2*
N 230 V 690
/
400 V
0 V 24 V
K1
K1
K5
K5
K3
K3
K3 K5
Fwd
2)
Off
3)
K1
T1 T2
2CDC 342 022 F0207
Control Panel
K3 = star
K5 = delta
K1 = main
Fault
external
supply
supply
inputs
* transparent
to the fieldbus
Local control via
digital inputs
1)
Multi-function input DI2 as fault input: 0 = fault (closed circuit signal)
2)
Fwd: Momentary-contact switch (On)
3)
Off: 0 = dominating Off (closed circuit signal)
7.5.1.2 Extended circuit
Main features
Parameters to be changed (4.3.4)
(based on default)
Contactor K3 (star) at output DO0 Control function = Star-delta starter 1
Contactor K5 (delta) at output DO1 Fault output = On
Contactor K1 (main) via auxiliary contacts of
K3 and K5
Check-back = Auxiliary contacts
DI2 Multi-function input = 001
Fault lamp at output DO2 Local operation via DIs = On, 002, 003, 004,
008 or 009
Check-back by aux.contacts (DI0, DI1) Set current 1
DI0, DI1, DI2 = Multi-function inputs e.g.
fault or stop inputs when parameterized
Overload protection parameters
Address via Control Panel or Addressing Set
Local operation via inputs DI4 and DI5
Remark: For this case of motor wiring the set current must be set to 58% of the nominal motor
current (3.2.3 and 4.3.4).