- 18 -UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
3.2.3 Motor current = Set current versus wiring
Have a look at the wiring of the motor to fi x the correct Set current for perfect motor protection.
Example:
For 3 (inner delta) wiring the parameter Current factor can be changed to 1.73 to get displayed the real
Set currents on the Control Panel and in the control system. The Delta 3 circuitry is normally used for
larger motors to reduce the current transformer size.
Fig. 3-4: Motor current = Set current versus wiring
Chapter 3.2.3~1
U2
W2
V2
V1 W1U1
UMC 22
U2W2 V2
V1 W1U1
400 V / 690 V
W2
U1
U2
V1 W1
V2
UMC 22
U2W2 V2
V1 W1U1
400 V / 690 V
V1 W1U1
W2
U2 V2
UMC 22
U2W2 V2
V1 W1U1
400 V / 690 V
Star
Power line: 690 V
Delta
Power line: 400 V
3 wiring
Power line: 400 V
Example for motor:
Motor rating plate
Example for motor:
Motor rating plate
Example for motor:
Motor rating plate
4.9 A / 2.8 A
4.9 A / 2.8 A 4.9 A / 2.8 A
Parameter
Set current = 2.80
Parameter
Set current = 4.90
Parameter
Set current = 2.80*
Terminal box Terminal box Terminal box
I
P
= 2.8 A / I
SC
= 2.8 A I
P
= 4.9 A / I
SC
= 4.9 A I
P
= 4.9 A / I
SC
= 2.8 A
I
SC
=
I
P
I
SC
=
I
P
I
SC
=
I
P
* 0.577
I
P
I
P
I
P
2CDC 342 063 F0203
I
P
= Actual current / phase
I
SC
= Set current
* Alternatively it is possible to set the parameter Current factor
to 1.7 and the parameter Set current to 4.9 A.