- 22 -UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
3.3.2 Address check
The parameter Address check is dedicated to be used particularily for drawer systems. If activated it
detects when - per hazard - drawers are exchanged and wrong drawers are inserted.
This chapters describes the addressing in general and the function if Address check is activated.
When switching on the combination UMC22-FBP FieldBusPlug 5 cases are possible:
Case 1:
Neither the UMC22-FBP nor the FieldBusPlug contains a valid address:
The UMC22-FBP does not start to operate and to communicate.
Case 2:
Only the UMC22-FBP contains a valid address:
The FieldBusPlug gets the address and saves it. Operation and communication starts.
Case 3:
Only the FieldBusPlug contains a valid address:
The UMC22-FBP gets the address and saves it. Operation and communication starts.
Case 4:
The UMC22-FBP and the FieldBusPlug contain the same address:
Operation and communication starts.
Case 5:
The UMC22-FBP and the FieldBusPlug contain different addresses:
The behaviour of the UMC22-FBP depends on the setting of the parameter Address check.
Case 5a:
Address check = Off (= 0) (default):
The FieldBusPlug stores the address received from the UMC22.
Operation and communication starts.
Case 5b:
Address check = On (= 1). Mainly used for Draw-out design.
Neither the operation nor the communication starts.
The Control Panel monitors alternating (3 seconds each):
Address of the UMC22-FBP
Address of the FieldBusPlug
Fault (F021) is set.
With the Control Panel the menu Change address has to be selected and the desired address
must be adjusted (8.).
After leaving this menu operation and communication starts immediately.
Both the FieldBusPlug and the UMC22-FBP store the adjusted address.
Remark:
If the adjusted FieldBusPlug address is not confi gured in the fi eldbus master the communication does not
start and the red LED on the FieldBusPlug monitors Fault.
Chapter 3.3.2~1