- 47 - UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Chapter 4.3.2~1
4.3.2 Single Parameter Transfer
Using the numeros of the Parameters
Para
No.
Qty.
Byte
Parameter name Defi nition / Range Default value
(text version)
Default
(digital)
take-over
after
1)
01 4 Set current 1 0.24-3200.00 A,
step: 0.01 A
0.5 A 50 motor off
02 2 Current factor 2-64000 %,
step: 1 %
100 % = 1 100
2)
motor off
03 4 Set current 2 0.24-3200.00 A,
step: 0.01 A
0.5 A 50 motor off
04 1 Trip class Class 5, Class 10, Class 20,
Class 30 (Value 0, 1, 2, 3)
Class 10 1 motor off
05 1 DI0 Multi-function input 000 to 048 Transparent 000 motor off
06 1 Phase loss protection Off (0), On (1), (2), (3), (4), (5), (6),
(7)
On 1 motor off
Please read the safety remark in subsection 4.3.4~13!
07 1 DI1 Multi-function input 000 to 048 Transparent 000 motor off
08 1 Low current threshold 5-100 % * Set current,
step: 5 %
50 % 10 motor off
09 1 High current threshold 100-800 % * Set current,
step: 5 %
150 % 30 motor off
10 2 Cooling time 30-3600 s,
step: 0.1 s
120 s 1200 motor off
11 1 Automatic fault reset Disabled (0),
Autoreset (1)
Disabled 0 motor off
12 1 Control function Transparent (1), Overload relay (2),
Direct starter (3), ...
Transparent 1 motor off
3
13 1 Check-back Auxiliary contontacts (1),
Motor current (2), Simulation (3)
Motor current 2 motor off
14 2 Start-up time 0 - 600 s,
step: 0.1 s
120 s 1200 motor off
15 1 Star-delta changeover
mode
Time (0),
Current (1)
Current 1 motor off
16 2 Star-delta starting time 1 - 3600 s,
step: 0.1 s
60 s 600 motor off
17 2 Reverse lock-out time 0.2 - 3600 s,
step: 0.1 s
2 s 20 motor off
18 2 Operating hours of
motor
0 - 65
.
535 h,
step: 1 h
0 0 (read only)
19 4 Number of starts 0 - 1000‘000,
step: 1
0 0 (read only)
20 1 Bus fault reaction Relais off (0),
Outputs retain status (1)
Relais off 0 motor off
21 1 DI2 Multi-function input 000 to 089 Transparent 000 motor off
1)
: but only when the internal fault bit is not set.
2)
: 1 is also regarded as 100 % due to the compatibility to older confi guration fi les (.GSD, .EDS...)
3)
: except overload relay, which needs a power cycle