- 140 -UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Chapter 8.2.1~1
8.2. Menu levels
8.2.1 Monitoring
Par.
No.
Menu
No.
Menu point name Display:
7-segm.
Default Range Description / remark take over
- 1.1
Show address
(4.3.4)
no depending
on bus typ
Actual slave address -
Invalid / no address
- 1.2
Actual current
Highest current of one of the 3 phases -
1.2.1 show
0 - 800 %
xx.xx A
xxx.x A
xxxx A
Actual current in % of Set current
% is displayed on the right side of
the display,
resolution on the bus 1/32 = 3.125 %
With cursor it can be changed to (and
back):
Actual current absolute
A is displayed on the right side of
the display, the position of the decimal
point is set automatically
- 1.3
Fault messages
(4.3.4)
FAULT on the left side of the display is
ashing.
Fault existing!
The menu goes directly to menu point
Fault.
-
1.3.x
1.3.1.1
1.3.y
1.3.1.1
...
rst fault
Acknowledge
next fault
Acknowledge
...
The fi rst of the existing faults is shown
with [ENTER].
Acnowledge of this fault with [ENTER].
The next existing fault is shown imme-
diately.
Acknowledge this fault with [ENTER].
...
No Fault existing!
1.3.1 Overload fault
Overload or phase loss has lead to
trip. Cooling time has started. As long
as the Cooling time is running the °C
on the disply fl ashes. Acknowledge is
possible when the Cooling time has
elapsed.
Restart of motor needs:
- Acknowledge and
- 01 transition of RUN FORWARD or
RUN REVERSE command
Remark:
Blocking causes also Overload fault. In
this case Cooling time is not started.
1.3.2 Motor blocked
Motor current over blocking current
threshold.
Assumption:
Parameter Blocking current threshold
is activated.