- 71 - UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
5.1 Main power lines (continued)
Chapter 5.1~3 and 5.2.~1
Accuracy class of the monitored
current
(range 50 to 200 %)
UMC22-FBP alone 3%
UMC22-FBP with provi-
ded current transformer
4%
Burden per phase ca. 30 m⏲
Frequency range 45-65 Hz
Frequency converters not allowed
Short-circuit protection Provided by external SCPD (Short Cir-
cuit Protection Device), e.g. MO, MCB,
MCCB or fuse.
Refer also to ABB coordination tables
(Internet).
Coordination tables, access via Internet
http://www.abbcontrol.fr/coordination_tables/TABLES5.asp
Cross section of lines acc. to the rated motor current refer-
ring EN/IEC 60947-1 and for particular
installation situation referring EN/IEC
60204 or VDE 298-4 resp.
5.2 Controller unit
Supply voltage 24 V DC (+30 % ... -20 %)
(19.2 ... 31.2 V DC) including ripple
Supply current
(incl. inputs, relays activated)
max. 160 mA (at 19.2 ... 31.2 V DC)
Total device dissipation max. 3.7 W
Reverse polarity protection yes
Number of digital inputs 6 (DI0 ... DI5)
relay outputs 3 (DO0 ... DO2)
PTC inputs 1 (T1-T2)
bus interfaces 1 (for connecting an ABB FieldBusPlug)
Control Panel interfaces 1 (to mount Control Panel ACS100-PAN)
Internal signal processing of control
function and other properties
Selectable by parameters,
see chapters 7 and 8
Parameter Setting via fi eldbus, via Control Panel,
see chapters 7 and 8
LEDs on the front green device ready for operation
red fault (trip, device fault etc.)
yellow motor current > 20 % of set current
Diagnosis see chapter 4.2.1