- 49 - UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Chapter 4.3.3~1
1)
: but only when the internal fault bit is not set.
2)
: 1 is also regarded as 100 % due to the compatibility to older confi guration les (.GSD, .EDS...)
3)
: except overload relay, which needs a power cycle
Para
No.
Qty.
Byte
Parameter name Defi nition / Range Default value
(text version)
Default
(digital)
take-over
after
1)
27 1 Emergency by PLC Off (0),
On (1)
Off 0 motor off
4.3.3 Transfer of the complete parameter set in one block
Wrd
No.
Byt
No.
Parameter name
Byte
weight
Defi nition / Range Default value
Default
(digital)
take-over
after
1)
0
0
Set current 1
high
0.24-3200.00 A,
step: 0.01 A
0.5 A 50 motor off
1
1
2
low3
2
4
Current factor
high
2-64000 %,
step: 1 %
1 100
2)
motor off
5 low
3
6
Set current 2
high
0.24-3200.00 A,
step: 0.01 A
0.5 A 50 motor off
7
4
8
low9
5
10 Trip class
Class 5, Class 10, Class 20,
Class 30 (Value 0, 1, 2, 3)
Class 10 1 motor off
11
DI0 Multi-function
input
000 to 048 Transparent 000 motor off
6
12
Phase loss protection
Off (0), On (1), (2), (3), (4), (5), (6),
(7)
On 1 motor off
Please read the safety remark in subsection 4.3.4~13!
13
DI1 Multi-function
input
000 to 048 Transparent 000 motor off
7
14 Low current threshold
50-100 % * Set current,
step: 5 %
50 % 10 motor off
15 High current threshold
100-800 % * Set current,
step: 5 %
150 % 30 motor off
8
16
Cooling time
high
30-3600 s,
step: 0.1 s
120 s 1200 motor off
17 low
9
18 Automatic fault reset
Disabled (0),
Autoreset (1)
Disabled 0 motor off
19 Control function
Transparent (1), Overload relay
(2), Direct starter (3), ...
Transparent 1 motor off
3)
10
20 Check-back
Auxiliary contacts (1),
Motor current (2), Simulation (3)
Motor current 2 motor off
21
Start-up time
high 0-600 s,
step: 0.1 s 120 s 1200 motor off
11
22
low
23
Star-delta changeover
mode
Time (0),
Current (1)
Current 1 motor off