- 42 -UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Chapter 4.2.4~1
4.2.4 Diagnosis - Details
Byte Bit Panel Short description Description
0
0 F016
OTS 1 0 but not
OLS (= Intermediate
position)
(Fault)
2)
Intermediate position is monitored: signal from open
torque switch has switched from 1 0 but signal
from open limit switch has not switched from 0 1.
Reason: e. g. connection to the torque switch has
been interrupted (closed circuit)
1 F015
CLS 1 0 not
within 3 s after open
command
(Fault)
2)
Signal from closed limit switch has not switched from
1 0 within 3 s after open command.
2 F014
OLS 1 0 not
within 3 s after clo-
se command
(Fault)
2)
Signal from open limit switch has not switched from 1
0 within 3 s after close command.
3 F013
CLS 1 0 without
open command
(Fault)
2)
Signal from closed limit switch has switched from 1
0 without an open command.
Reason: e.g. faulty contact.
4 F012
OLS 1 0 without
close command
(Fault)
2)
Signal from open limit switch has switched from 1
0 without a close command).
Reason: e.g. faulty contact.
5 F011
Fault signal on DI0,
DI1 or DI2
(Fault)
At least one multi-function input has a fault signal (0-
signal) e.g. from a thermistor module.
Assumption:
At least one multi-function input is parameterized as
Multi-function input = 001 (Fault signal always / not
delayed)
(closed-circuit principle).
6 F010
Self test failed
(Fault)
Self test has failed or was started during motor run-
ning.
Remark:
This fault can not be acknowledged.
7 F009
Same time OLS and
CLS
(Fault)
2)
Run-time: max. allowed running time open  close.
For adjustment use parameter Star-delta starting time.
1 0 F008
Relay 0
check-back fault
(Fault)
1)
No 1-signal from auxiliary contact at input DI0 within
300 ms after switching on the contactor or 1-signal at
input DI0 even if contactor is not switched on.
Supposition:
Parameter Check-back = Auxiliary contacts.
CTS 1 0 but not
CLS (= Intermediate
position)
(Fault)
2)
Intermediate position is monitored:
Signal from closed torque switch has switched from 1
0 but signal from closed limit switch has not swit-
ched from 0 1.
Reason: e.g. connection to the torque switch has
been interrupted (closed circuit)
1)
For all control functions ecxept Actuator 1-4!
2)
Only for control function Actuator 1-4!