- 150 -UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Chapter 8.2.3~1
8.2.3 Edit 2
Par.
No.
Menu
No.
Menu point name Display:
7-segm.
Default Range Description / remark take over
- 3.1
Change
password
(4.3.4)
-
3.1.1 show / change
0000 0001-9999 Show and change password. Entering
0000 resets the password to none.
12 3.2
Control function
(4.3.4)
during
motor
off
1)
3.2.1 Transparent
Trans. Direct access to DIs/DOs via fi eldbus
3.2.2 Overload relay
Similar to overload relay
3.2.3 Direct starter
Direct start with check-back
3.2.4 Reversing starter
Reversing start with check-back
3.2.5 Star-delta starter 1
Star-delta start via 2 DOs,
with check-back
3.2.6 Pole-changing
starter 1
Pole-changing start witch check-back
3.2.7 Actuator 1
Actuator start type 1 witch check-back
3.2.8 Actuator 2
Actuator start type 2 witch check-back
3.2.9 Actuator 3
Actuator start type 3 witch check-back
3.2.10 Actuator 4
Actuator start type 4 witch check-back
3.2.11 Star-delta starter 2
Star-delta start via 3 DOs,
with check-back
1)
beside overload relay, which requiers a power cycle