- 146 -UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Chapter 8.2.2~1
8.2.2 Edit 1
Par.
No.
Menu
No.
Menu point name Display:
7-segm.
Default Range Description / remark take over
- 2.1
Password
Skipped to menu point Password
panel control if the password (default
0000) has not been changed. Else
enter password
immedia-
tely
2.1.1 enter password
* * * *
0 0001-9999 - At any time back with [MENU]
without saving.
- First position fl ashes, change with
[Cursor], press [ENTER], .....,
4th number fl ashes, change with
[CURSOR], after position 4 (4!) save
with [ENTER].
- 2.2
Passoword panel
control
Local control is always possible, inde-
pendent of the status of the command
AUTO MODE.
If local control is activated, RUN
commands from the control system
are ignored.
Entering and leaving local control does
not infl uence the actual status of the
outputs of the UMC22
Before removing the Control Panel
this menu must be left, otherwise the
control system can not switch on the
motor.
-
2.2.1 switch motor on
and off
change direction
Off is always possible and dominating
via control system, Control Panel and,
if parametrized, via digital input DI0.
Toggle on/off of the relay outputs, on
incl. start procedure and check-back.
Remark:
Reversing starter:
Selection of the other direction is
possible if
- motor is stopped AND
- Reversing lock-out time has elapsed.
Pole-changing starter:
Switch over to the other speed is exe-
cuted immediately (changeover time
min. 50 ms).
Display: Speed 1=FWD Speed 2=REV.