EasyManua.ls Logo

ABB UMC22-FBP - Control Panel - Direct Panel Control

ABB UMC22-FBP
168 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
- 34 -UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Chapter 3.7.3~1
3.7.3 Control Panel - Direct panel control
"Direct panel control" is dedicated to be used after commissioning. It prepares simplifi ed start and stop of
the motor and acknowledge of faults e.g. for less skilled user of an installation.
"Direct panel control" is possible if the parameter Local control = 003 or 004 or 005 (L.003, L.004, L.005)
& the control station sends the command AUTO MODE = 0.
Remark:
If the connection to the control system is interrupted (control station problem or fi eldbus interrupted) the
command AUTO MODE is regarded as 0.
If "Direct panel control" is activated it is still possible to enter other menu points of the Control Panel e.g.
to change parameters, etc.
Regarding the three-level access only the Monitoring level has been changed:
LOC
%
FWD REV
LOC
FAULT
FWD
LOC
%
OUTPUT FWD
LOC
FWD
FAULT
°C
LOC
A
OUTPUT FWD
current absolute
start,
stop
(toggle)
stop,
reverse
(toggle)
fault
flashing
example of fault
run
cooling
time
running
Supposed: Parameter Local control = 003, 004 oder 005
AND
Control station sends command AUTOMODE = 0
- OR -
Connection to control station interrupted
Leave to other menu points e.g.
to Set current.
Comes back to display current
in % after 5 min if no button is
pressed.
Power-up
of the UMC22
Mounting of the
Control Panel
Acknowledge
and back with
when fault is
corrected
toggle
2CDC 342 014 F0207
FWD: forward
or
REV: reverse
current in %
Fig. 3-15: Control Panel ACS100-PAN - Operation level for "Direct panel control"