- 50 -UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
4.3.3 Transfer of the complete parameter set in one block (continued)
Wrd
No.
Byt
No.
Parameter name
Byte
weight
Defi nition / Range Default value
Default
(digital)
take-over
after
1)
12
24
Star-delta starting
time
high
1-3600 s,
step: 0.1 s
60 s 600 motor off
25 low
13
26
Reverse lock-out time
high
0.2-3600 s,
step: 0.1 s
2 s 20 motor off
27 low
14
28 reserved - - -
29 reserved - - -
15
30 reserved - - -
31 Emergency by PLC
Off (0),
On (1)
Off 0 motor off
16
32 reserved - - - -
33 reserved - - - -
17
34 reserved - - - -
35 reserved - - - -
18
36 Address check
Off (0),
On (1)
Off 0
power
up
37 Bus fault reaction
Relays off (0),
Outputs retain status (1)
Relays off 0 motor off
19
38
DI2 Multi-function
input
000 to 089 Transparent 000 motor off
39 Local control
Off (0), On (1), 002 (2), 003 (3),
004 (4), 005 (5), 006 (6) , 007 (7) ,
008 (8) , 009 (9)
Off
0 motor off
20
40
Blocking current
threshold
0-800 % * Set, current,
step: 5 %
800 % 160 motor off
41 Fault output
Off (0), On (1),
blink (3)
Off 0 motor off
1)
: but only when the internal fault bit is not set.
Chapter 4.3.3~2