UMC22-FBPFieldBusPlug / Issue: 02.2008
V 6
Universal Motor Controller UMC22-FBP
Software version 4.0
Par.
No.
Menu
No.
Menu point name Display:
7-segm.
Default Range Description / remark take over
22 3.5
Local control
(4.3.4)
This parameter prepares for:
- Local operation via digital inputs
AND/OR
- Direct panel control via Control
Panel (8.1.2).
Remarks:
- Off Input DI5 can be prepared as
closed-circuit signal or as true sig-
nal.
- Local control (direct panel control
and/or local operation via DIs) is
activated if
~ command AUTO MODE = 0 is
send by the control system -OR-
~ communication to the control
system is interrupted.
during
motor off
3.5.1 No local control
No loc.
control
No local control of any kind
3.5.2 Local operation
only via DI3, DI4,
DI5 (1)
DI3: Reverse (true, pulse)
DI4: Forward (true, pulse)
DI5: Off (closed circuit, pulse)
No Direct panel control via Control
Panel
3.5.3 Local operation
only via DI3, DI4,
DI5 (2)
DI3: Reverse (true, pulse)
DI4: Forward (true, pulse)
DI5: Off ( true, pulse)
No Direct panel control via Control
Panel
3.5.4 Local operation via
DI3, DI4, DI5 (1)
Direct panel
control via Control
Panel
DI3: Reverse (true, pulse)
DI4: Forward (true, pulse)
DI5: Off (closed circuit, pulse)
Direct panel control via Control Panel
3.5.5 Local operation via
DI3, DI4, DI5 (2)
Direct panel
control via Control
Panel
DI3: Reverse (true, pulse)
DI4: Forward (true, pulse)
DI5: Off ( true, pulse)
Direct local control via Control Panel
3.5.6 Direct panel
control only
Only Direct panel control via Control
Panel