- 25 - UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
3.4.1 Regular start and stop (continued)
Start the motor via:
Control system, command RUN FORWARD or RUN REVERSE:
Possible if the control system has set the command bit AUTO MODE = 1
& the Control Panel is not active (not in "Password panel control" mode).
Control Panel:
"Password panel control":
Always possible and dominating if the Control Panel is in "Password panel control" mode.
This mode is password protected and can be enabled and entered via the Control Panel only.
In this mode the Control Panel can seize the activity under all circumstances.
Run - Off toggle, display shows OUTPUT when running
"Direct panel control":
Possible if the parameter Local control = 003 or 004 or 005 or 006 or 007
& the control station sends the command AUTO MODE = 0.
Details see 3.7.3 and 8.2.3
Digital inputs:
"Local operation via DIs":
Possible if the parameter Local control = on or 002 or 003 or 004 or 006 or 007 or 008 or 009
& the Control Panel is not active (not in "Password panel control" mode)
& the control station sends the command bit AUTO MODE = 0 in the command telegram.
Details see 4.3.4 and 8.2.3
Remark:
If the connection to the control system is interrupted (control station problem or fi eldbus interrupted) the
command AUTO MODE is regarded as = 0.
Stop the motor via:
Control system, command OFF:
Under all circumstances dominating against RUN FORWARD or RUN REVERSE,
independend of the parameter Local control and the command AUTO MODE=0
Control Panel:
"Password panel control":
Always possible and dominating if the Control Panel is in "Password panel control" mode.
This mode is password protected and can be enabled and entered via the Control Panel only.
In this mode the Control Panel can seize the activity under all circumstances.
Off when running, change direction when off Run - Off toggle
"Direct panel control":
Possible if the parameter Local control = 003 or 004 or 005 or 006 or 007
& the control station sends the command AUTO MODE = 0.
Digital input DI5:
"Local operation via DIs":
Always possible and dominating if the parameter Local control = on or 002 or 003 or 004 or 006 or
007 or 008 or 009 , except actuator 1 ... 4.
Remark:
Off is always dominating under above named suppositions.
Details see 4.3.4 and 8.2.3
Chapter 3.4.1~2