- 44 -UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
Chapter 4.2.4~3
4.2.4 Diagnosis - Details (continued)
Byte Bit Panel Short description Description
2
0-
Run-time exeeded
(Warning)
2)
1-
Emergency start
prepared
(Warning)
Emergency start is prepared via control system or via
digital input (Emergency start with 01 transition of a
RUN signal via control system or via digital input).
2 buSy
Self test running
(Warning)
Self test is running
3-- -
4°C
Cooling time
running
(Warning)
Cooling time is running.
5-- -
6-
Motor current low
threshold
(Warning)
Motor current is below the low threshold current.
Assumption:
Parameter Low current threshold is activated.
7-
Motor current high
threshold
(Warning)
Motor current is above the high threshold current.
Assumption:
Parameter High current threshold is activated.
3
0-7 -
Parameter number,
Selft test fault
number
Neither:
Parameter numbers above 27 are not accepted (para-
meter numbers are only possible for buses that allow
access to single parameters)
Nor:
Self test fault number (for service only)
Else:
0 F017
PTC temperature
Motor temperature to high
1 F018
PTC wire break
One of the PTC feed lines is broken
2 F019
PTC short-circuit
3 F020
Earth fault
4 F022
Fault on DI0
External fault signaled via DI0
5 F023
Fault on DI1
External fault signaled via DI1
6 F024
Fault on DI2
External fault signaled via DI2
7-
Additional
trip information
Trip because of phase loss or unbalance
1)
For all control functions ecxept Actuator 1-4!
2)