- 63 - UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.2008
V 6
4.3.4 Parameter - Details in alphabetical order (continued)
Chapter 4.3.4~13
Parameter
name /
Parameter
number
Remark
Parameter value
Description of parameter values
Control
system
(digital
value if
different)
Control
Panel
Number of
starts
19
Control system can only read the value - supposed the fi eldbus can transmit the value.
Change value is only possible via Control Panel (menu point: noSt)!
0-1'000'000
0000-
1000
Remark:
All starts are counted but the last 3 digit positions are not displayed on the
Control Panel.
The displayed range of 0000 - 1000 corresponds with 0 - 1.000.000.
Number of
trips
25
Control system can only read the value - supposed the fi eldbus can transmit the value.
Change value is only possible via Control Panel (menu point: notr)!
0-255
0000-
0255
Remark:
All trips are counted and displayed on the Control Panel.
Operating
hours of motor
18
Control system can only read the value - supposed the fi eldbus can transmit the value.
Change value is only possible via Control Panel (menu point: oPho)!
0-65'535
00.00-
65.53
Remark:
All hours are counted but the last digit position is not displayed on the
Control Panel.
The displayed range of 00.00 - 65.53 corresponds with 0 - 65.535.
Parameter lock
Accessible via Control Panel (menu point: PA.Lo) only!
Locks writing the parameters via control system / fi eldbus and via Control Panel.
- P.EnA
Parameter enabled (= default):
Parameter lock is not activated: Writing of parameters enabled
- P.Loc
Parameter locked:
Parameter lock is activated: Writing of parameters locked
Parameter
transfer
Accessible via Control Panel (menu point: PA.tr) only!
All parameter information - exept the Slave address, Operation hours, Number of starts and Numb-
er of trips - can be read out from or written into the UMC22 by the Control Panel.
- PA.rE
Read parameters:
Control Panel reads out all parameter information from an UMC22.
- PA.SE
Set parameters:
Control Panel overwrites all parameter information in the UMC22.
Password
Accessible via Control Panel (menu point: PASS) only!
Will be skipped - direct to the next menu point - if the default password has not been changed
before.
-
0001-
9999