- 80 -
UMC22-FBP
Universal Motor Controller UMC22-FBP
Software version 4.0
FieldBusPlug / Issue: 02.0008
V 6
7.1.3 Interface and data overview
Hardware Inputs / Outputs
Chapter 7.1.3~1 Transparent
Terminal 13 14 15 16 17 18
Device input
(to bus)
DI0 DI1 DI2 DI3 DI4 DI5
Terminal 7 8 9
Device output
(from bus)
DO0 DO1
DO2
2)
(fault output)
Monitoring telegram, digital
Bit No. 7 6 5 4 3 2 1 0
Byte 0 WARNING FAULT - - - - - -
Byte 1
DI5
(UMCinput)
DI4
(UMCinput)
DI3
(UMCinput)
DI2
(UMCinput)
DI1
(UMCinput)
DI0
(UMCinput)
--
Monitoring telegram, analog
Byte 0 and Byte 1: Motorcurrent in % of set current
Command telegram, digital only
Bit No. 7 6 5 4 3 2 1 0
Byte 0 -
FAULT
RESET
-
PREPARE
EMERGENCY
START
SELF
TEST
---
Byte 1
DO2
1)
(UMC output)
DO1
(UMC output)
DO0
(UMC output)
----
Diagnosis telegram
Bit No. 7 6 5 4 3 2 1 0
Fault
Byte 0
-
Self test failed
F010
2)
Fault signal
on DI0, DI1
or DI2
1)
F011
2)
-----
Fault
Byte 1
Overload (trip)
fault
trip
2)
-
Communi-
cation fault
F003
2)
Parameter out
of range
F004
2)
----
Warning
Byte 2
Motor current
high threshold
1)
Motor current
low threshold
1)
-
Self test
running
buSy
2)
-
Self test
running
buSy
2)
Emergency
start
prepared
-
Warning
Byte 3
If Parameter out of range: Pamameter number (leading two stages of the parameter, e.g. "02" Current factor)
If Self test fauled: Self test error number (only for service)
In all other cases:
Phase loss
trip
2
Fault on DI2
F024
2)
Faut on DI1
F023
2)
Fault on DI0
F022
2)
Earth fault
F020
2)
PTC
short-circuit
F019
2)
PTC
wire break
F018
2)
PTC
temperature
F017
2)
1)
depending on parameterization
2)
displayed on the Control Panel Busdata details see 4.2.2.