IST Series UPS (10kVA-200kVA)
User Manual A Technical Specifications
91
Model
Index
10kVA
20kVA
30kVA
40kVA
50kVA
60kVA
80kVA
100kVA
140kVA
160kVA 200kVA
Touch screen display
Three-phase input voltage, input frequency, three-phase output
voltage, load, battery voltage, battery charge & discharge current,
each unit output current and inner temperature, parameter setting,
hIST7ory record, etc.
LED display Work status and fault indication of UPS.
Alarm function Alarm for input abnormal, battery low-voltage, overload, fault, etc.
Communication function
Provides dry contact communication and RS485, and it can also equip
with SNMP to realize the smart monitor for the UPS.
Battery monitor function
(optional)
MMBM-3 battery monitor manage system, realizes the work status
monitor of single battery.
Protection function
Protect for output short-circuit, output over-voltage/ under-voltage,
overload, over-temperature, battery under-voltage, etc.
EMC Meet the provision of GB7260.2-2009
Noise (dB)
<70 (measured away from the front cabinet for 1m)
Cooling way Forced wind-cooling
Work temperature (
)
0~40
Size (W×D×H) (mm)
320*840*86
7
450*840*96
7
450*840*1400 600*900*1600
Weight (kg) 120 160 210 242 300 342
Specifications are subject to change without prior notice.