Code Description Note Type
AL094
EVD - LOP 2 alarm 2
AL095
EVD - MOP 2 alarm 2
AL096
EVD - Low overheating 2 2
AL097
EVD - Low suction temperature 2 2
AL100
Inverter – envelop init error The compressor is working out of envelope 3
AL101
Inverter – fault 3
AL102
Inverter – overcurrent 3
AL103
Inverter - over voltage 3
AL104
Inverter – over temperature
 inverter temperature too high
 check the liquid valve and/or refrigerant load. The valve activates
when the oil exceeds 100°C and deactivates when it goes below
95°C
3
AL105
Inverter – under voltage 3
AL106
Inverter – power supply fault  failure of a phase or imbalance between phases 3
AL107
Inverter – hardware fault 3
AL108
Inverter – temperature sensor fault
 inverter temperature sensor fault. Check the oil sensor and motor
sensor
3
AL109
Inverter – hardware conguration error incorrect hardware conguration 3
AL110
Inverter – conguration data error  incorrect software conguration 3
AL111
Inverter – conguration parameter error  incorrect inverter parameters 3
AL112
Inverter – motor thermal overload  motor winding temperature above limits 3
AL113
Inverter – motor overload 3
AL115
Inverter – motor phase failed 3
AL116
Inverter – high oil temperature
 high oil temperature (check oil heater)
 warning if greater than 115°C
 fault if greater than 120°C
 reset alarm if less than 105°C
3
AL117
Inverter – low oil temperature 3
AL118
Inverter - Compressor Short Cycling
 compressor starting is requested before the minimum time
between two starts has passed. This occurs only at the Warning level
3
AL119
Inverter – envelope error The compressor is working out of envelope 3
AL120
Inverter – serial control timeout  power request from card pCO5+ to inverter timeout 3
AL121
Inverter – communication error 3
AL122
Inverter – datalog error 3
AL123
Inverter – pressure sensor fault 3
The alarms read by the compressor inverter card can have three levels, as indicated in the example window:
Inverter
AL: XXX U:01
(Warning/Critical/Fault)
ALARM NAME
Warning: pre-alarm condition
Critical: becomes Fault after 30’
Fault: compressor OFF manual reset alarm