Radio channel. It activates/deactivates the wireless association module of the system.
Condensation protection (only available for thermostat Blueface on installations with cooling radiant control). Enables
to select the protection level against condensation: Very high, high, medium (by default), low and very low. If
necessary, it can be activated for 1h.
*Note: In Very Low configuration, the humidifier will be automatically activated if the relative humidity level is higher than
55% in any active zone.
Reset system (only available for master thermostat Blueface). Resets the system and returns to factory settings. To
reconfigure the thermostats, please check System start-up).
Information (only for Think thermostats). It provides information about:
- Zone: Firmware, zone, association, actuator o communications status.
- System: Firmware, configuration and information about the controllers.
- Devices: Displays what elements are connected to the system.
- Webserver: Firmware, IP address, gateway, MAC and PIN.
ZONE PARAMETERS
Associated outputs. It displays and allows you to select the control outputs associated with the thermostat.
Thermostat settings. Use this parameter to define the thermostat as Master or Zone.
*Note: It cannot be configured as Master if there is already another Master thermostat.
Use mode. The thermostats can be set in Basic or Advanced mode. They are set in advanced mode by default. These
are the parameters you can control in basic mode:
- On/Off.
- Set-point temperature.
- Fan Speed
If you need to reset the thermostat to advanced mode, access the advanced configuration menu and then activate the
advanced use mode.
Control stages. Enables/disables cooling and heating stages in a selected zone or in all zones of the system.
Offset. Allows you to correct ambient temperature that is measured in the various areas or in all of them, due to
deviations by sources of heat/cold nearby, with a correction factor between - 2,5ºC and 2,5ºC in steps of 0,5ºC. It is in
0ºC by default.
Reset thermostat. Resets the thermostat returning to Setup menu (see section Zone Configuration menu - Blueface
Thermostat).