EasyManua.ls Logo

Allen-Bradley 193-DNENCAT - Ethernet Link Object - CLASS CODE 0 Xf6

Allen-Bradley 193-DNENCAT
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
106 Rockwell Automation Publication 193-UM014C-EN-P - August 2016
Appendix B EtherNet/IP and DeviceNet Information
For single port devices, one instance of the TCP/IP interface object is
supported. For dual port devices, two instances of the TCP/IP interface object
are supported.
Table 61 - TCP/IP Object Class Instances
The following common services are implemented for the TCP/IP interface
object.
Table 62 - TCP/IP Interface Object Common Services
Ethernet Link Object — CLASS CODE 0xF6
The following class attributes are supported for the Ethernet Link object.
Table 63 - Ethernet Link Object Class Attributes
The following one instance of the Ethernet Link object is supported.
Attribute ID Access Rule Name Data Type Value
1GetStatusDWORD
2Get
Configuration
Capability
DWORD 0x00000014
3 Get/Set
Configuration
Control
DWORD
0=Configuration from NVS
2=Configuration from DHCP
4Get
Physical
Link Object
Struct of:
UINT
Padded
EPATH
For a single port device: 2 words
20 F6 24 01 (ENet Link Object Inst 1)
For dual port device: NULL
5 Get/Set
Interface
Configuration
Struct of:
UDINT
UDINT
UDINT
UDINT
UDINT
STRING
IP Address
Network Mask
Gateway Address
Primary DNS
Secondary DNS
Default domain name for not fully
qualified host names
6 Get/Set Host Name STRING
8 Get/Set TTL Value USINT
Time to live value for EtherNet/IP
multicast packets
9 Get/Set
Multicast
Config
Struct of:
USINT
USINT
UINT
UDINT
Allocation Control
Reserved
Number of multicast addresses to allocate
(1-4)
Multicast starting address
Service Code
Implemented for:
Service Name
Class Instance
0x01 No Yes Get_Attributes_All
0x0E Yes Yes Get_Attribute_Single
0x10 No Yes Set_Attribute_Single
Attribute ID Access Rule Name Data Type Value
1 Get Revision UINT 1

Table of Contents

Related product manuals