Rockwell Automation Publication 193-UM014C-EN-P - August 2016 81
Chapter 9
Device Parameters
Introduction
The EtherNet/IP communication auxiliary module provides parameters to let
you view the status and configure the DeviceNet scanner with RSNetWorx™
for DeviceNet if you do not want to use the internal web server of the
EtherNet/IP communication auxiliary module. Tabl e 10
lists the 14 available
parameters.
Table 10 - Parameter List
Parameter Programming
Parameter Listing
The details for each of the 14 available parameters are listed below.
Table 11 - Parameter 1 — Scanner Status
1 Scanner Status 8 SL Entry Size
2 SL Entry 1 Status 9 Device Keys
3 SL Entry 2 Status 10 Scanlist Config
4 SL Entry 3 Status 11 ADR Record
5 SL Entry 4 Status 12 ADR Enable
6 SL Entry 5 Status 13 DNet IO RPI
7 SL Entry 6 Status 14 DNet IO Inhibit
IMPORTANT Parameter setting changes to the EtherNet/IP communication auxiliary
module take effect immediately even during a “running” status.
Description Access Rule Data Type Units
Value
Min. Max. Default
Provides the status of the
Devicenet scanner.
Get WORD — 0 16383 0
Bit
0 On Line 3 No Scanner Messages 6 Initializing
1 Illegal Scan List 4 Transmit Failure 7 Duplicate MAC Failure
2 No Network Messages 5 In Idle Mode 8 Bus Off