46 Rockwell Automation Publication 193-UM014C-EN-P - August 2016
Chapter 4 Add Devices to the DeviceNet Network
User-Defined
If there are more than six DeviceNet devices on the network, you can select up
to six DeviceNet devices to scan. Follow the steps below to select specific
DeviceNet devices for the scan list.
1. From the EtherNet/IP communication auxiliary module web page,
navigate to Scan List>Configuration>Scan List. The EtherNet/IP
communication auxiliary module reads the available DeviceNet
modules on the DeviceNet network.
2. Select the DeviceNet device in the Network Who screen to be added to
the Scan List. The >> button becomes highlighted.
3. Click >> to move the selected device into the Scan List.
4. Repeat steps 2 and 3 to add five additional DeviceNet devices.
5. Click Save at the bottom right of the screen.