EasyManua.ls Logo

Allen-Bradley 193-DNENCAT - Page 36

Allen-Bradley 193-DNENCAT
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36 Rockwell Automation Publication 193-UM014C-EN-P - August 2016
Chapter 3 Configure the DeviceNet Network
3. Type the size of the Scan List I/O Entry in the field.
The entry size determines the number of input and output bytes that the
EtherNet/IP communication auxiliary module scans from each of the
scanned devices. The maximum Scan List I/O Entry Size supported is
50 bytes; the default value is 8 bytes.
4. If necessary, adjust DNet IO Request Packet Interval (RPI) and DNet
IO Inhibit.
DNet IO RPI determines the time it takes for data to be requested;
DNet IO Inhibit is the time used on DeviceNet Change of State (COS)
I/O. Both of these parameters are measured in milliseconds.
5. Select the “Scan List” tab from the configuration menu to change the
DeviceNet node address of the EtherNet/IP communication auxiliary
module.
NOTE:
Auto Device Replacement (ADR) is discussed in Chapter 6
, Automatic Device Recovery or
Replace.
NOTE:
Electronic keying is implemented on all scan list entries. Electronic keys are captured
when a scan list is configured from the EtherNet/IP communication auxiliary module
web page. The proper setting of the electronic keying becomes more important with
ADR functions and replacing units in the network.

Table of Contents

Related product manuals