66 Rockwell Automation Publication 193-UM014C-EN-P - August 2016
Chapter 7 Automation Controller Communication
4. Enter a name for the EtherNet/IP communication auxiliary module.
The name creates a tag in RSLogix 5000 that can be used to read and
write data from the devices being scanned by the EtherNet/IP
communication auxiliary module.
5. Select Data-INT for the Comm Format. The Data-INT format
represents the data from the EtherNet/IP communication auxiliary
module as a field of 16-bit values.
6. Set the Connection Parameters. I/O data is accessed using Input
Instance 101 and Output Instance 100. The size of the input connection
and the output connection shall correspond to the size of the chosen
instance. The configuration Assembly Instance is 102.
NOTE: In this example, configuration data is not used. Thus, the data size is set to 0