Rockwell Automation Publication 193-UM014C-EN-P - August 2016 83
Device Parameters Chapter 9
Table 15 - Parameter 5 — SL Entry 4 Status
Table 16 - Parameter 6 — SL Entry 5 Status
Table 17 - Parameter 7 — SL Entry 6 Status
Table 18 - Parameter 8 — SL Entry Size
Description Access Rule Data Type Units
Value
Min. Max. Default
Provides the status of the fourth
scan list entry in the DeviceNet
scanner.
Get WORD — 0 2047 0
Bit
0 On Line 4 No Such Device 8 Device Went Idle
1 Connection Timeout 5 Fragment Error
9
Automatic Device Replacement
Error
2 Keying Mismatch 6 Slave Initialization Error
3 Wrong Data Size 7 I/O Data Overflow 10 Acknowledgement Timeout
Description Access Rule Data Type Units
Value
Min. Max. Default
Provides the status of the fifth
scan list entry in the DeviceNet
scanner.
Get WORD — 0 2047 0
Bit
0 On Line 4 No Such Device 8 Device Went Idle
1 Connection Timeout 5 Fragment Error
9
Automatic Device Replacement
Error
2 Keying Mismatch 6 Slave Initialization Error
3 Wrong Data Size 7 I/O Data Overflow 10 Acknowledgement Timeout
Description Access Rule Data Type Units
Value
Min. Max. Default
Provides the status of the sixth
scan list entry in the DeviceNet
scanner.
Get WORD — 0 2047 0
Bit
0 On Line 4 No Such Device 8 Device Went Idle
1 Connection Timeout 5 Fragment Error
9
Automatic Device Replacement
Error
2 Keying Mismatch 6 Slave Initialization Error
3 Wrong Data Size 7 I/O Data Overflow 10 Acknowledgement Timeout
Description Access Rule Data Type Units
Value
Min. Max. Default
Defines the number of bytes to be
scanned for I/O data from each
DeviceNet Device.
Get/Set USIN T Bytes 1 50 8