Appendix B   Module Tag Definitions
5069-OB16F Module Tags
This section describes the tags that are associated with the 5069-OB16F 
modules.
Configuration Tags
Table 83 describes the 5069-OB16F module configuration tags.
DC INPUT
5069-IB16
DC OUTPUT
5069-OB16
ANALOG INPUT
5069-IY4
SA Power MOD Power
ANALOG OUTPUT
5069-OF8
DC INPUT
5069-IB16
Standard Modules
Table 83 - 5069-OB16F Configuration Tags
 Name Size Definition Valid Values
Ptxx.FaultMode BOOL Selects the behavior the output channel takes if a 
communication fault occurs. FaultValue defines the value 
to go to when set to user-defined value.
• 0 = Hold last state
• 1 = Go to a user-defined value
Ptxx.FaultValue BOOL Defines the value that the output assumes if a 
communication fault occurs when FaultMode = 0.
• 0 = Off
• 1 = On
Ptxx.ProgMode BOOL Selects the behavior that the output takes when 
transitioned into Program mode. ProgValue defines the 
value to go to when set to user-defined value.
• 0 = Hold last state
• 1 = Go to a user-defined value
Ptxx.ProgValue BOOL Defines the value that the output takes when the 
connection transitions to Program mode if the ProgMode 
bit is set to "User-Defined Value".
• 0 = The output state is Off during Program 
mode.
• 1 = The output state is On during Program 
mode.
Ptxx.FaultFinalState BOOL If FaultValueStateDuration is nonzero, determines the final 
Output state after the configured FaultValueStateDuration 
time-out occurs.
• 0 = The output state is Off after the 
FaultValueStateDuration time expires.
• 1 = The output state is On after the 
FaultValueStateDuration time expires.
Ptxx.ProgramToFaultEn BOOL Determines if an output transitions to the Fault Mode if 
the connection faults while in Program Mode.
• 0 = Stay in Program Mode
• 1 = Go to Fault mode
Ptxx.NoLoadEn BOOL Enables no load detection for output channels. • 0 = Disable
• 1 = Enable
Ptxx.FaultValueStateDuration SINT This value determines the length of time the Fault Mode 
state is held before the FaultFinalState being applied.
• 0 = Hold forever (default).
• 1, 2, 5, or 10 seconds