274 Rockwell Automation Publication 5069-UM004A-EN-P - April 2019
Appendix C      Application and Wiring Examples for Safety Modules
5069-IB8S or 5069-IB8SK 
Module Wiring Diagrams
When the module is wired as shown, it is suitable for applications that are rated 
up to, and including, Category 3 as defined in ISO 13849-1.
5069-IB8S
Safety Input 0
Safety Input 1
Safety Input 2
Safety Input 3
Safety Input 4
Safety Input 5
Safety Input 6
Safety Input 7
Test Output 0
Test Output 0
Test Output 1
Test Output 1
Test Output/Muting Output 2
Test Output/Muting Output 2
Test Output/Muting Output 3
Test Output/Muting Output 3
COM
COM
OSSD1
OSSD2
Light 
Curtain
24V DC SELV/PELV-
listed power supply
+
–
Channel Connections
The diagram shows devices that are connected to safety 
input channels 0, 1, 6, and 7. You are not restricted to 
using only those channels.
You can connect devices to any safety input channel or 
combination of channels as needed.
SA Power
Connections to an external power supply that provides 
SA power via the SA Power RTB on one of the following:
• Compact GuardLogix 5380 controller
• 5069-AENTR or 5069-AEN2TR EtherNet/IP™ Adapter
• 5069-FPD field potential distributor
IMPORTANT: Remember the following:
• The 5069-IB8S and 5069-IB8SK modules use DC SA 
power. You must connect DC power to the 
component, that is, controller, adapter, or field 
potential distributor, that provides SA Power to the 
modules.
• If you install modules in a system that use AC SA 
power and DC SA power, you must install them on 
separate SA power buses.
• You use a 5069-FPD field potential distributor to 
establish a new SA Power bus in a system. SA Power 
buses are isolated from each other. To keep the 
modules on separate SA Power buses, complete the 
following steps.
1. Install the modules that use one type of SA power, 
for example DC, to the right of the adapter or 
controller, that is, the first SA Power bus.
2. Install the 5069-FPD field potential distributor to 
establish a second SA Power bus.
3. Install the modules that use the other type of SA 
power, for example AC, on the second SA Power 
bus.
Important: 
• The switches are suitable for applications that are 
rated up to, and including, SIL CL3, PLe, Cat. 3.
• The light curtain is suitable for applications that are 
rated up to, and including, SIL CL3, PLe, Cat. 4.