Module Configuration Attributes
Chapter 5
Rockwell Automation Publication MOTION-RM003I-EN-P - February 2018 479
"AC/DC Non-Regenerative" represents the class of devices that convert AC
input power to DC output power. They do not have the capability to
transfer energy back to the AC main supply.
"AC/DC Regenerative" represents the class of devices that convert power
between AC and DC sources. They have the capability to transfer energy
bidirectionally between an AC main supply and DC bus in both directions.
These devices provide active control to regulate energy transfer between AC
main and DC bus.
"DC/DC Non-Regenerative" represents the class of devices that convert
DC input power to DC output power. They do not have the capability to
transfer energy back to the primary DC bus supply.
"DC/DC Regenerative" represents the Class of devices that convert power
between two DC sources. They have the capability to transfer energy
between a primary DC bus and a secondary DC bus in both directions.
These devices may provide active control to regulate energy transfer
between the primary and secondary buses.
DC Bus Output Voltage Set Point
Usage Access T Data Type Default Min Max Semantics of Values
Optional - BD Set
REAL 0 0
Volts
Sets the reference voltage used to actively regulate the DC Output Bus Voltage of
the converter when in the Running state.
Shunt Regulator Resistor Type
Usage Access T Data Type Default Min Max Semantics of Values
Optional - BD Set
USINT 0 - - Enumeration:
0 = Internal
1 = External
2-255 = (reserved)
This attribute defines whether an Internal or External Shunt resistor is used.
External Shunt Regulator ID
Usage Access T Data Type Default Min Max Semantics of Values
Optional - BD Set
INT -1 -1 32767 -1 = None
0 = Custom
1-32767 = Shunt Regulator ID

Table of Contents

Other manuals for Allen-Bradley ControlLogix

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley ControlLogix and is the answer not in the manual?

Allen-Bradley ControlLogix Specifications

General IconGeneral
CommunicationEtherNet/IP, ControlNet, DeviceNet, DH+
I/O CapacityUp to 128, 000 I/O points (varies by configuration)
RedundancySupported (with specific modules)
Programming SoftwareRockwell Automation Studio 5000 Logix Designer
Operating Temperature0°C to 60°C (32°F to 140°F)
Programming LanguagesLadder Logic, Function Block Diagram, Structured Text, Sequential Function Chart
ModularityYes
CertificationsUL, CE
Processor TypeMultiple options available, including standard, safety, and extreme environment processors
Power SupplyMultiple options available, including standard and redundant power supplies with various voltage ranges (e.g., 24V DC, 120/240V AC)

Related product manuals