Rockwell Automation Publication 2097-UM002D-EN-P - April 2017 145
Upgrade the Kinetix 350 Drive Firmware Appendix B
6. Click OK.
The Configure driver dialog box appears.
7. Type the IP address of your drive.
8. Click OK.
The new Ethernet driver appears under Configured Drivers.
9. Click Close.
10. Minimize the RSLinx application dialog box.
Upgrade Firmware
Follow these steps to select the drive module to upgrade.
1. Open your ControlFLASH software.
You can access the ControlFLASH software by either of these methods:
In RSLogix 5000® software from the Tools menu, choose
ControlFLASH.
Choose Start>Programs>FLASH Programming Tools>
ControlFLASH.