Chapter 1
Process Control Instructions
218 Rockwell Automation Publication 1756-RM006K-EN-P - November 2018
Input Parameters Data
Type
Description Values
ProgCV1ManualReq BOOL Program-Manual mode request for CV1.
Set TRUE by the user program to request
Manual mode.
When ProgValueReset is TRUE, the function
block resets the input to FALSE.
Default = FALSE
ProgCV2ManualReq BOOL Program-Manual mode request for CV2.
Set TRUE by the user program to request
Manual mode.
When ProgValueReset is TRUE, the function
block resets the input to FALSE.
Default = FALSE
ProgCV3ManualReq BOOL Program-Manual mode request for CV3.
Set TRUE by the user program to request
Manual mode.
When ProgValueReset is TRUE, the function
block resets the input to FALSE.
Default = FALSE
ProgCV1OverrideRe
q
BOOL Program-Override mode request for CV1.
Set TRUE by the user program to request
Override mode.
When ProgValueReset is TRUE, the function
block resets the input to FALSE.
Default = FALSE
ProgCV2OverrideRe
q
BOOL Program-Override mode request for CV2.
Set TRUE by the user program to request
Override mode.
When ProgValueReset is TRUE, the function
block resets the input to FALSE.
Default = FALSE
ProgCV3OverrideRe
q
BOOL Program-Override mode request for CV3.
Set TRUE by the user program to request
Override mode.
When ProgValueReset is TRUE, the function
block resets the input to FALSE.
Default = FALSE
ProgCV1HandReq BOOL Program-Hand mode request for CV1.
Set TRUE by the user program to request Hand
mode. This value will usually be read as a
digital input from a hand/auto station.
When ProgValueReset is TRUE, the function
block resets the input to FALSE.
Default = FALSE
ProgCV2HandReq BOOL Program-Hand mode request for CV2.
Set TRUE by the user program to request Hand
mode. This value will usually be read as a
digital input from a hand/auto station.
When ProgValueReset is TRUE, the function
block resets the input to FALSE.
Default = FALSE
ProgCV3HandReq BOOL Program-Hand mode request for CV3.
Set TRUE by the user program to request Hand
mode. This value will usually be read as a
digital input from a hand/auto station.
When ProgValueReset is TRUE, the function
block resets the input to FALSE.
Default = FALSE