224 File Instructions
The source and destination file types must be the same except bit (B) and
integer (N); they can be interchanged. It is the address that determines the
maximum length of the block to be copied, as shown in the following
table:
IMPORTANT
You cannot use indirect addressing with: S, MG, PD,
RTC, HSC, PTO, PWM, STI, EII, BHI, MMI, CS, IOS, and
DLS files.
Maximum Lengths for the COP Instruction
Source/Destination Data Type Range of Length Operand
1 word elements (ie. word) 1 to 128
2 word elements (ie. long word) 1 to 64
3 word elements (ie. counter) 1 to 42
42 word elements (ie. string) 1 to 3