EasyManuals Logo

Allen-Bradley MicroLogix 1100 Instruction Set Reference Manual

Allen-Bradley MicroLogix 1100
616 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #281 background imageLoading...
Page #281 background image
Publication 1763-RM001C-EN-P - October 2009
Process Control Instruction 281
PD Data File
The PID instruction implemented by the MicroLogix 1100 controllers is
virtually identical in function to the PID implementation used by the
Allen-Bradley SLC 5/03 and higher processors. Minor differences primarily
involve enhancements to terminology. The major difference is that the
PID instruction now has its own data file. In the SLC family of processors,
the PID instruction operated as a block of registers within an integer file.
The Micrologix 1100 PID instruction utilizes a PD data file.
You can create a PD data file by creating a new data file and classifying it
as a PD file type. RSLogix automatically creates a new PD file or a PD
sub-element whenever a PID instruction is programmed on a rung. The
PD file then appears in the list of Data Files as shown in the illustration.
Each PD data file has a maximum of 255 elements and each PID
instruction requires a unique PD element. Each PD element is composed
of 20 sub-elements, which include bit, integer and long integer data. All of
the examples in this chapter use PD file 10 sub-element 0.
PD file created by
RSLogix 500.
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive

Table of Contents

Other manuals for Allen-Bradley MicroLogix 1100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley MicroLogix 1100 and is the answer not in the manual?

Allen-Bradley MicroLogix 1100 Specifications

General IconGeneral
Processor32-bit
Programming SoftwareRSLogix 500
MountingDIN rail or panel mount
Power Supply24V DC
TypeCompact PLC
Digital Inputs12
Digital Outputs8
Analog Inputs4 (depending on model)
Analog OutputsOptional with expansion module
Programming LanguageLadder Logic
Operating Temperature0 to 55 °C (32 to 131 °F)
SeriesMicroLogix

Related product manuals