506 Protocol Configuration
DF1 Half-Duplex
Protocol
DF1 Half-Duplex protocol provides a multi-drop single master/multiple
slave network. In contrast to the DF1 Full-Duplex protocol,
communication takes place in one direction at a time. You can use the
RS-232 port on the MicroLogix controller as both a Half-Duplex
programming port, and a Half-Duplex peer-to-peer messaging port.
MicroLogix 1100controller supports Half-Duplex modems using RTS/CTS
hardware handshaking.
DF1 Half-Duplex supports up to 255 devices (addresses 0 to 254, with
address 255 reserved for master broadcasts). Note: When configuring a
message instruction, set the target node address to -1 for broadcast
messages.
Broadcast messages are handled as follows:
DF1 Half-Duplex Master Driver Broadcast Messages
A broadcast write command initiated by the DF1 half-duplex master is
received and executed by all DF1 half-duplex slaves. A broadcast write
command received by the DF1 half-duplex master after polling a DF1
half-duplex slave is received, acknowledged and re-broadcast without
being executed by the DF1 half-duplex master. It is treated like any other
slave-to-slave command, except that no acknowledgement is expected
after re-broadcast.
DF1 Half-Duplex Slave Driver Broadcast Messages
When a broadcast write command is initiated by a DF1 half-duplex slave,
it is queued up just like any other MSG command until it receives a poll
from the DF1 half-duplex master. After transmitting the broadcast write
command, the DF1 half-duplex slave receives an acknowledgement that
the DF1 half-duplex master received the packet without error. When the
DF1 half-duplex master re-broadcasts the broadcast write command, the
initiating DF1 half-duplex slave receives and executes the command along
with all of the other slave nodes receiving the broadcast packet. No
acknowledgement or reply is returned.
Choosing a Polling Mode for DF1 Half-Duplex Master
A master station can be configured to communicate with slave stations in
either Message-based polling mode or Standard polling mode. The pros
and cons of each polling mode are described below.
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive

Table of Contents

Other manuals for Allen-Bradley MicroLogix 1100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley MicroLogix 1100 and is the answer not in the manual?

Allen-Bradley MicroLogix 1100 Specifications

General IconGeneral
Processor32-bit
Programming SoftwareRSLogix 500
MountingDIN rail or panel mount
Power Supply24V DC
TypeCompact PLC
Digital Inputs12
Digital Outputs8
Analog Inputs4 (depending on model)
Analog OutputsOptional with expansion module
Programming LanguageLadder Logic
Operating Temperature0 to 55 °C (32 to 131 °F)