Publication 1763-RM001C-EN-P - October 2009
274 Using Interrupts
EII Function File Sub-Elements
EII Program File Number (PFN)
PFN (Program File Number) defines which subroutine is called (executed)
when the input terminal assigned to EII:0 detects a signal. A valid
subroutine file is any program file (3 to 255).
The subroutine file identified in the PFN variable is not a special file
within the controller. It is programmed and operated the same as any
other program file. From the control program perspective it is unique, in
that it is automatically scanned based on the configuration of the EII.
EII Error Code (ER)
Any ER (Error Code) detected by the EII sub-system is displayed in this
register. The table below explains the error codes.
Sub-Element Description Address Data Format Type User Program
Access
PFN - Program File Number EII:0.PFN word (INT) control read only
Sub-Element Description Address Data Format Type User Program
Access
ER - Error Code EII:0.ER word (INT) status read only
EII Error Codes
Error
Code
Recoverable Fault
(Controller)
Description
1 Invalid Program File
Number
Program file number is less than 3, greater than 255, or does not
exist
2 Invalid Input
Selection
Valid numbers must be 0, 1, 2, 3, 4, 5, 6, or 7.
3 Input Selection
Overlap
EIIs cannot share inputs. Each EII must have a unique input.
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive

Table of Contents

Other manuals for Allen-Bradley MicroLogix 1100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley MicroLogix 1100 and is the answer not in the manual?

Allen-Bradley MicroLogix 1100 Specifications

General IconGeneral
Processor32-bit
Programming SoftwareRSLogix 500
MountingDIN rail or panel mount
Power Supply24V DC
TypeCompact PLC
Digital Inputs12
Digital Outputs8
Analog Inputs4 (depending on model)
Analog OutputsOptional with expansion module
Programming LanguageLadder Logic
Operating Temperature0 to 55 °C (32 to 131 °F)
SeriesMicroLogix

Related product manuals