EasyManuals Logo

Allen-Bradley MicroLogix 1100 Instruction Set Reference Manual

Allen-Bradley MicroLogix 1100
616 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #367 background imageLoading...
Page #367 background image
Publication 1763-RM001B-EN-P - April 2007
Communications Instructions 367
Data Table Address
This variable defines the starting address in the local controller. Valid file
types for the Data Table Address are shown below:
Size in Elements
This variable defines the amount of data (in elements) to exchange with
the target device.
Message Read Message Write
Bit (B)
Timer (T)
Counter (C)
Control (R)
Integer (N)
Floating Point (F)
(1)
Long Word (L)
String (ST)
(3)
(1) Message Type must be 500CPU or PLC5. The Local File Type and Target File Type must both be Floating Point.
Output (O)
Input (I)
Bit (B)
Timer (T)
Counter (C)
Control (R)
Integer (N)
Floating Point (F)
(1)
Long Word (L)
String (ST)
(2)
(3)
Real-Time Clock (RTC)
(4)
(2) 485CIF write-to-485CIF only for MicroLogix 1100 OS Series A FRN 3 or earlier.
(3) MicroLogix 1100 OS Series B FRN 4 or later.
(4) 500CPU write RTC-to-Integer or RTC-to-RTC only.
TIP
Only Bit (B) and Integer (N) file types are valid for
Modbus Command messages. Modbus bit commands
require a starting bit address for the Data Table Address.
Floating Point (F) and Long (L) file types are valid for
Modbus Command messages for Holding Registers
(commands 03, 06 and 16) when Data is configured for
32 bit.
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive

Table of Contents

Other manuals for Allen-Bradley MicroLogix 1100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley MicroLogix 1100 and is the answer not in the manual?

Allen-Bradley MicroLogix 1100 Specifications

General IconGeneral
Processor32-bit
Programming SoftwareRSLogix 500
MountingDIN rail or panel mount
Power Supply24V DC
TypeCompact PLC
Digital Inputs12
Digital Outputs8
Analog Inputs4 (depending on model)
Analog OutputsOptional with expansion module
Programming LanguageLadder Logic
Operating Temperature0 to 55 °C (32 to 131 °F)
SeriesMicroLogix

Related product manuals