Publication 1763-RM001B-EN-P - April 2007
Communications Instructions 419
Routing Information File : Routing Information File must be
Routing Information File.
Break Connection (BK) : This bit has no impact on the operation.
IP Address of MultiHop : IP Address of MultiHop must be local IP
Address (127.0.0.1 or its own IP Address).
Email Functionality
This section describes how to configure a SMTP email message when you
use Ethernet communication channel 1 of the MicroLogix 1100.
Setup SMTP Configuration File
While the processor is selected to MicroLogix 1100 Series B, “SMTP Client
Enable” check box is shown in the Ethernet Channel Configuration tab. If
this check box is checked, SMTP configuration page will be appeared.
Otherwise, SMTP configuration page will not be appeared.
You must setup SMTP configuration before sending SMTP messages.
TIP
If you sent a message with Data Table Offset 0, 1, or 3 to
change IP Address, Subnet Mask, or Gateway Address
respectably, these addresses will be applied after
power-cycle. If you want to change IP Address, Subnet
Mask, and Gateway Address right away, you must send
another Ethernet message to the local IP Address with
Data Table Offset 10.
WARNING
If you sent an Ethernet message to the local IP Address
with Data Table Offset 10 and the different IP Address
has been configured, all the Ethernet connection is
broken.
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive

Table of Contents

Other manuals for Allen-Bradley MicroLogix 1100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley MicroLogix 1100 and is the answer not in the manual?

Allen-Bradley MicroLogix 1100 Specifications

General IconGeneral
Processor32-bit
Programming SoftwareRSLogix 500
MountingDIN rail or panel mount
Power Supply24V DC
TypeCompact PLC
Digital Inputs12
Digital Outputs8
Analog Inputs4 (depending on model)
Analog OutputsOptional with expansion module
Programming LanguageLadder Logic
Operating Temperature0 to 55 °C (32 to 131 °F)
SeriesMicroLogix

Related product manuals