EasyManuals Logo

Allen-Bradley MicroLogix 1100 Instruction Set Reference Manual

Allen-Bradley MicroLogix 1100
616 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #52 background imageLoading...
Page #52 background image
Publication 1763-RM001C-EN-P - October 2009
52 Function Files
The real-time clock does not allow you to load or store invalid date or
time data.
Real-Time Clock Accuracy
The following table indicates the expected accuracy of the real-time clock
for various temperatures.
RTC Battery Operation
The real-time clock uses the same replaceable battery that the controller
uses. The RTC Function File features a battery low indicator bit (RTC:0/
BL), which shows the status of the replacement battery. When the battery
is low, the indicator bit is set (1). This means that the battery wire
connector could be disconnected or if the battery is connected, the battery
may be ready to fail in the next two days. In the latter case, the
replacement battery needs to be replaced with a new one. When the
battery low indicator bit is clear (0), the battery level is acceptable.
TIP
Use the Disable Clock button in your programming
device to disable the real-time clock before storing a
module. This decreases the drain on the battery during
storage.
Real-Time Clock Accuracy at Various Temperatures
Ambient Temperature
Accuracy
(1)
(1) These numbers are worst case values over a 31 day month.
0°C (+32°F) -13 to -121 seconds/month
+25°C (+77°F) +54 to -54 seconds/month
+40°C (+104°F) +29 to -78 seconds/month
+55°C (+131°F) -43 to -150 seconds/month
ATTENTION
Operating with a low battery indication for more than 14
days (or 8 hours without the battery) may result in
invalid RTC data if power is removed from the controller.
efesotomasyon.com - Allen Bradley,Rockwell,plc,servo,drive

Table of Contents

Other manuals for Allen-Bradley MicroLogix 1100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley MicroLogix 1100 and is the answer not in the manual?

Allen-Bradley MicroLogix 1100 Specifications

General IconGeneral
Processor32-bit
Programming SoftwareRSLogix 500
MountingDIN rail or panel mount
Power Supply24V DC
TypeCompact PLC
Digital Inputs12
Digital Outputs8
Analog Inputs4 (depending on model)
Analog OutputsOptional with expansion module
Programming LanguageLadder Logic
Operating Temperature0 to 55 °C (32 to 131 °F)
SeriesMicroLogix

Related product manuals