DE-3000 IOI 7-17
All rights reserved © ALTRONIC, LLC 2017
31
CHAN ~20
INPUT CLASS A ©B C
92 SECONDS TIME
DELAY ON START-UP
RUNNING
PRESS TO
VIEW THE
INPUT CLASS
OF CHANNEL
20
TENS
To view the next channel number, press the NEXT key until the arrow points to
the channel number. Select another channel number by using the
UNITS or
UNITS keys to increase or decrease the channel by one or use the
TENS or
TENS key to increase or decrease the channel by ten and press ENTER.
15.11 To edit global values, select EDIT SAFETY SHUTDOWN from main menu. Select
EDIT GLOBAL VALUES from next menu.
EDIT SETPOINTS
EDIT INPUT CLASS
~EDIT GLOBAL VALUES
MORE MENUS
RUNNING
EDIT GLOBAL VALUES
TEST TIME 100 SEC
RUNNING
PRESS TO
EDIT THE
GLOBAL
VALUES
ENTER
To change the test time, use the
UNITS or
UNITS keys to increase or decrease the
value by one. Use the
TENS or
TENS keys to increase or decrease the value by
ten. Press the ENTER key to save the new value and advance to the next value.
15.12 To edit the output configuration, choose EDIT SAFETY SHUTDOWN from the
main menu. Select MORE MENUS from the following menu. Finally, select OUT-
PUT CONFIG. from the last menu.
EDIT SETPOINTS
EDIT INPUT CLASS
EDIT GLOBAL VALUES
~MORE MENUS
RUNNING
CHAN ~20
INPUT CLASS A ©B C
92 SECONDS TIME
DELAY ON START-UP
EDIT SETPOINTS
EDIT INPUT CLASS
~EDIT GLOBAL VALUES
MORE MENUS
EDIT GLOBAL VALUES
TEST TIME 100 SEC
EDIT SETPOINTS
EDIT INPUT CLASS
EDIT GLOBAL VALUES
~MORE MENUS