PN 9000-165-VE, Rev P
Optional Blowback Conguration
The Blowback Conguration screen can be accessed from the Conguration
menu on the AMEVision controller. For this menu to appear, Blowback must
rst be enabled on the Sensor Conguration screen.
The WDG-V allows you to choose from four Blowback trigger types:
• Manual Only – You must initiate the Blowback manually from the Utility
Menu. See below.
• Timed – Blowback will occur continuously at a predetermined time inter-
val (i.e. every 2 hours). It is recommended that the time interval be at least
1 hour to prevent valve coil overheating.
• Flow – Blowback will automatically be triggered if the ow reading from
the ow sensor drops below a user-dened threshold.
• Timed and Flow – Blowback will occur at the predetermined time inter-
val unless ow drops below the user-dened threshold in which case the
Blowback will trigger due to low ow.
Low Flow triggered Blowback will only occur once per hour.
Blowback Interval – Time in hours between automatic timed Blowback triggers.
Blowback Recovery – Time in seconds when the oxygen and combustible
readings are frozen after a Blowback has been triggered to allow the system to
return to equilibrium.
Low Flow Threshold – Flow reading in % at which a Blowback is triggered.
Figure 5-1.
Blowback Conguration
screen.
Optional Blow Back Conguration | 5-1