Smoke Control Programs
5-25 Infinity Smoke Control Guide
TOC
FL3SADmp.Fail = (Time - PlantTimer[14]) > MaxDamperTime
‘ Plant 15
If not (((SMKDMPRS Fl3.RASDmp = On) & (SMKDMPRS
Fl3.RASDmp.Cls <> On)) or ((SMKDMPRS Fl3.RASDmp = Off)
& (SMKDMPRS Fl3.RASDmp.Opn ~
<> On))) then PlantTimer[15] = Time
FL3RADmp.Fail = (Time - PlantTimer[15]) > MaxDamperTime
‘ Plant 16
If not (((SMKDMPRS Fl4.SASDmp = On) & (SMKDMPRS
Fl4.SASDmp.Cls <> On)) or ((SMKDMPRS Fl4.SASDmp = Off) &
(SMKDMPRS Fl4.SASDmp.Opn ~
<> On))) then PlantTimer[16] = Time
FL4SADmp.Fail = (Time - PlantTimer[16]) > MaxDamperTime
‘ Plant 17
If not (((SMKDMPRS Fl4.RASDmp = On) & (SMKDMPRS
Fl4.RASDmp.Cls <> On)) or ((SMKDMPRS Fl4.RASDmp = Off)
& (SMKDMPRS Fl4.RASDmp.Opn ~
<> On))) then PlantTimer[17] = Time
FL4RADmp.Fail = (Time - PlantTimer[17]) > MaxDamperTime
‘ Plant 18
If not (((Flr2TCX VAVDmp = On) & (Flr2TCX VAVDmp.Opn <>
On)) or ((Flr2TCX VAVDmp = -On) & (Flr2TCX VAVDmp.Cls <>
On))) then ~
PlantTimer[18] = Time
FL2VAV.Fail = (Time - PlantTimer[18]) > MaxDamperTime
‘ Plant 19
If not (((Flr3TCX VAVDmp = On) & (Flr3TCX VAVDmp.Opn <>
On)) or ((Flr3TCX VAVDmp = -On) & (Flr3TCX VAVDmp.Cls <>
On))) then ~
PlantTimer[19] = Time
FL3VAV.Fail = (Time - PlantTimer[19]) > MaxDamperTime
‘ Plant 20
If abs(Flr4TCX Damper - Flr4TCX Damper Position) < 0.005
then PlantTimer[20] = Time
FL4VAV.Fail = (Time - PlantTimer[20]) > MaxDamperTime
‘ Turn ON FSCS Fail LEDs for a Weekly Self Test Failure of a
Dedicated Controller
If AH3Sfan.ST.Fail then AH3Sfan.Fail = On
If FL2SADmp.ST.Fail then FL2SADmp.Fail = On