EasyManuals Logo

Andover Controls Infinity User Manual

Default Icon
190 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #159 background imageLoading...
Page #159 background image
System Operation
Andover Controls Corporation 6-9
TOC
The Weekly Self-Test
A weekly self-test will be performed on all of the dedicated controllers
in the smoke control system.
Non-dedicated controllers in the system do not get a weekly self-test.
Their operation is verified by the “comfort level” in the areas that they
serve.
In the example used in the previous chapter, the weekly self-test was
performed when the following criteria were met:
The system is not in a smoke control mode.
The Weekday is Sunday through Friday.
The Hour is between 0 and 4.
The system has not already been self-tested this week.
Therefore, assumming the system is not in a smoke control mode, the
weekly self-test will be performed just after midnight on saturday
(weekday = sunday, time = 00:00).
If a piece of equipment fails the self-test, the failure will get latched, the
FSCS fail indicator for that piece of equipment will turn ON, the FSCS
audible annunciator will turn ON, and the Status4 (Self-Test Failure)
indicator on the CX9200 will turn ON.
In order to clear the self-test failure, the MASTER KEY must be turned
ON, and the CLEAR FAULTS button must be pushed.
The equipment that failed the self-test should be tested immediately to
determine why it failed. Once the cause of the failure is determined, the
equipment must be repaired.
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Andover Controls Infinity and is the answer not in the manual?

Andover Controls Infinity Specifications

General IconGeneral
BrandAndover Controls
ModelInfinity
CategoryController
LanguageEnglish

Related product manuals