Installation and Layout
Andover Controls Corporation 3-5
TOC
The TCX840 and TCX850 series
Only an Andover Controls’ Listed transformer may be used to supply the 24V AC
input power for the TCX840 and TCX850 series. These transformers must be placed
in a Listed enclosure and must be wired according to the National Electric Code, as
well as any state or local regulations.
Table 3-1 lists the step-down transformers that are available from Andover Controls.
All of the Input and Output wiring on the TCX840 and TCX850 series must remain in
the same room.
The TCX860/865 series
Only an Andover Controls’ Listed transformer may be used to supply the 24V AC
input power for the TCX860/865 series. These transformers must be placed in a List-
ed enclosure and must be wired according to the National Electric Code, as well as
any state or local regulations.
Table 3-1 lists the step-down transformers that are available from Andover Controls.
All of the Input and Output wiring on the TCX860/865 series must remain in the same
room.
The Infilink 200
Any cables connected to the RS-232 port must be less than 20 feet in length, and must
be enclosed in conduit.
The Infilink 210
The Infilink 210 must be used to electrically isolate the Infinet controllers that are
performing smoke control from the non-smoke control Infinet controllers. This is
Table 3-1. Listed 24V Step-down Transformers
Voltage PRI:SEC VA Rating Part Number
Primary and
Secondary
Connections
115V : 24V 40 VA 01-2100-378 Solderless Lug
115V : 24V 40 VA 01-2100-323 Wires
277V : 24V 50 VA 01-2100-379 Solderless Lug
208/240V : 24V 40 VA 01-2100-407 Wires
Technical Manuals Online! - http://www.tech-man.com