EasyManuals Logo

Andover Controls Infinity User Manual

Default Icon
190 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #112 background imageLoading...
Page #112 background image
Smoke Control Programs
5-36 Infinity Smoke Control Guide
TOC
Programs for Controlling the System
Main
Type:
Program
FlowType:
Looping
AutoStart:
True
Description:
The main sequencing program. This program
determines what the entire system is doing by calling the other
programs and functions.
Code:
Initialize:
Zone1.SMK, Zone2.SMK, Zone3.SMK, Zone4.SMK and ~
STRWL.SMK = Off
MaxDamperTime = 60 ‘Seconds
MaxFanTime = 45 ‘Seconds
MaxCtlrTime = 10 ‘Seconds
FSCSLinkActive = False
Horn = Off
SelfTested = True
Print “*** Smoke Control System Initialized at “ ; Time ; “ ***”
Goto MainLoop
MainLoop:
FireAlarmCheck()
NetStatus()
PilotLights()
PlantFaultCheck()
Run FSCS_Interface to Read Switches and Update LEDs
If FSCSLinkActive is False then
FSCSLinkActive = True
Run FSCS_Interface
Endif
‘Run HornControl
If HornControl Status is not Active then Run HornControl
Run ClearFaults if Fault.Clear Button is Pushed
If Fault.Clear and ClearFaults Status is not Active then Run ~
ClearFaults
Check if time for Weekly self test. Run Self-Test if There are no
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Andover Controls Infinity and is the answer not in the manual?

Andover Controls Infinity Specifications

General IconGeneral
BrandAndover Controls
ModelInfinity
CategoryController
LanguageEnglish

Related product manuals