FIREFIGHTER’S SMOKE CONTROL STATION
OPERATING INSTRUCTIONS
For Use by Authorized Personnel Only
LED INDICATORS:
RED -
ALARM
has been received for the Zone
AMBER - Equipment
FAILURE
- Controller communications
FAULT
or
OVERRIDE
GREEN -
FAN
is
ON
-
DAMPER
is
OPEN
YELLOW -
DAMPER
is
CLOSED
Press the LAMP TEST button to test all Indicators. Replace faulty Indicators.
Press the CLEAR FAULTS button to clear Equipment or Controller faults.
The MASTER KEY must be ON in order to clear the faults.
THE MASTER KEY:
OFF -
DISABLE
Override Switches,
ENABLE
Audible Alarm
ON -
ENABLE
Override Switches,
DISABLE
Audible Alarm
All Override Switches should be in the AUTO position before turning
the MASTER KEY ON.
OVERRIDE SWITCHES:
AUTO - Equipment or Zone is under
Automatic
control
ON - Force the Fan
to turn
ON
OFF - Force the Fan to turn
OFF
OPEN - Force the Damper to
OPEN
CLOSE - Force the Damper to
CLOSE
PRESS -
Pressurize
the entire Zone
EXHAUST -
Exhaust
the entire Zone
In the event of trouble, contact your local service representative:
Name: ___________________________________________________
Address: _________________________________________________
Telephone: _______________________________________________
These Instructions should be framed and placed adjacent to the FSCS for ready reference.