Infinity Smoke Control System Components
Andover Controls Corporation 2-15
TOC
Design Guidelines
In order to have the FSCS built to your specifications, you will need to
supply the following:
An accurate drawing of the smoke control system. This drawing will
be used to create the FSCS front panel graphic.
A second copy of the FSCS drawing indicating the colors of the
status indicators.
A third copy of the FSCS drawing indicating the colors that are to be
used for the front panel graphic. Consult Automation Displays, Inc.
for a list of options.
Specify whether you need a flush-mount or a surface-mount panel.
Specify whether or not you need a transparent cover for the FSCS.
Specify whether or not you need a terminal block wired to the FSCS
inputs, to be used for Zoned Wiring to the Fire Panel.
Automation Displays, Inc. will provide you with a copy of the FSCS
drawing that indicates the I/O numbers that correspond to each LED
output and each switch input on the FSCS. Each 2 position switch
requires 1 input and each 3 position switch requires 2 inputs.
The FSCS you order from Automation Displays Inc. will contain the
following:
An Automation displays’ Autoface IV graphic door with a keylock.
Switches and Status Indicators for each piece of smoke control
equipment.
A “Master” keyswitch, a “Clear Faults” push-button, a “Lamp Test”
push-button and a sonalert audible annunciator.
An Automation Displays’ Q-Card CPU board with the “Andover
Data Interface” firmware that is wired to an RS232 Protection PCB.
An Automation Displays’ 80 Point Driver card for every 80 status
indicators.
An Automation Displays’ 80 Point Driver card for reading the FSCS
switches. A 2 position switch requires 1 input and a 3 position switch
requires 2 inputs. A Switch Protection PCB is also included.
A 5V DC power supply for the Q-Card, the 80 Point Driver cards,
and the FSCS Status Indicators.
Refer to Chapter 5 for a drawing of an example FSCS graphic.