EasyManua.ls Logo

Atlas Copco GA 160 VSD

Atlas Copco GA 160 VSD
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Toutlet = 55.8 + (141 / (4.2 x 4)) = 64.2°C
Total pressure drop on waterside is (1):
pd = (4.23 x 4²) + (1.62 x 4) = 74 kPa = 0.74 bar
Example point Y for a GA VSD working at 1500 RPM, when max RPM is 3000:
dT = 90-36 = 54°C
RPM
v
= 1500
RPM
max
= 3000
dT
v
= 54 x (1500/3000) = 27 °C
Q = 4.2 x 0.6 x 27 = 68 kW
Example point Z
Compressor unit: GA160-50Hz
Working pressure: 14 bar / 200 psi
Water flow: 1 l/s / 2.12 cfm
Water inlet temperature: 60°C / 140 °F
Water outlet temperature: 87.8°C / 190 °F
The formula to calculate the amount of recovered energy results in (2):
4.2 x 1 x (87.8-60) = 117 kW
The outlet temperatures for a water flow of 1 l/s can be calculated backwards from formula (2):
Toutlet = 60 + (117 / (4.2 x 1)) = 87.8°C
Total pressure drop on waterside is (1):
pd = (4.23 x 1²) + (1.62 x 1) = 5.85 kPa = 58.5 mbar
This proves that it is possible to work at higher temperatures, but with less heating power.
The temperature of the vessel can be set to 100°C as well. The installation can work in a higher curve,
to obtain a higher water outlet temperature. This setting must be done by a service technician of Atlas
Copco.
Example point below the lowest curve
Instruction book
2920 1728 05 25

Table of Contents

Related product manuals