Compressor type Voltage Cable size Remark
GA 110 VSD 460 2x(3x AWG4/0+AWG3) 90 ˚C insulation cable at 46
˚C ambient
GA 110 VSD 575 2x(3x AWG2/0+AWG4) 90 ˚C insulation cable at 46
˚C ambient
GA 132 - 160 VSD 460 2x(MCM250+AWG2) 90 ˚C insulation cable at 46
˚C ambient
GA 132 - 160 VSD 575 2x(AWG3/0+AWG4) 90 ˚C insulation cable at 46
˚C ambient
Maximum fuses
50 Hz IEC Pack compressors
Compressor type
Voltage
V
Frequency
Hz Approval
Water-
Cooled Air-Cooled
Type
GA 110 VSD 380 50 IEC
3x315 A 3x315 A DIN 43 620
size 3; high
speed fuse.
Fuse type:
AR
GA 110 VSD 400 50 IEC
3x315 A 3x315 A DIN 43 620
size 3; high
speed fuse.
Fuse type:
AR
GA 110 VSD 500 50 IEC
3x250 A 3x250 A DIN 43 620
size 3; high
speed fuse.
Fuse type:
AR
GA 132 VSD 380 50 IEC 3x400 A 3x400 A
DIN 43 620
size 3; high
speed fuse.
Fuse type:
AR
GA 132 VSD 400 50 IEC 3x400 A 3x400 A
DIN 43 620
size 3; high
speed fuse.
Fuse type:
AR
GA 132 VSD 500 50 IEC 3x315 A 3x315 A
DIN 43 620
size 3; high
speed fuse.
Fuse type:
AR
GA 160 VSD 380 50 IEC 3x500 A 3x500 A
DIN 43 620
size 3; high
speed fuse.
Fuse type:
AR
Instruction book
2920 1728 05 87