5 Bottom Blowdown
Page 98 Mk8 MM Expansion Features Installation and Set-Up Guide 04.09.2016
Figure 5.5.ii Bottom Blowdown Configuration
Press on to add a blowdown time. Press and drag to the left or right to adjust this time. Use the
buttons to increase and decrease the time/number of repeats. The bottom blowdowns
can be schedule at 5 minute intervals within the following ranges:
Configuration Range
Duration of blowdown 1 – 60s
Number of repeats for the blowdown 1 – 10
Time between repeats 1 – 60s
Number of schedule blowdowns 1 – 10 over 24hour period
To remove a blowdown time press on and drag this up, and then press
to remove this
blowdown time from the schedule.
Once the blowdown times have been set, press to save the blowdown times, and then press
to leave the bottom blowdown configuration screen.
Press set to save and then press exit.